350 kcmil THHN Copper Ampacity
350 kcmil copper THHN: 350A base at 90°C, 310A usable after 110.14(C) termination limit.
Base350A
Usable310A
NEC Table310.16
Full derating calculation
Applications
350 kcmil copper is commonly used for large commercial feeders (260-310A) and industrial motor feeders.
Voltage drop by distance
| Distance (ft) | 240V Drop | % Drop | Verdict |
|---|---|---|---|
| 50 ft | 1.1V | 0.5% | OK |
| 75 ft | 1.7V | 0.7% | OK |
| 100 ft | 2.3V | 0.9% | OK |
| 150 ft | 3.4V | 1.4% | OK |
| 200 ft | 4.5V | 1.9% | OK |
| 250 ft | 5.7V | 2.4% | OK |
| 300 ft | 6.8V | 2.8% | OK |
Requirements vary by state. NEC edition, licensing, permits, and GFCI rules differ by jurisdiction. Check your state or pick it below for personalized info across WireRef.
Important: For reference only. Not a substitute for a licensed electrician. Electrical work can cause serious injury, death, fire, or property damage if performed incorrectly. Always hire a licensed electrician for electrical work, especially for service upgrades, panel work, and 240V circuits. Values are derived from NFPA 70 (NEC) for educational purposes. Always verify against your locally adopted NEC edition and amendments - local jurisdictions may enforce stricter requirements. WireRef provides reference information only and is not responsible for work performed based on this content. NEC® is a registered trademark of the National Fire Protection Association. Free NEC access via NFPA · OSHA Electrical Safety · Terms of use.