ModerateNEC 2023 · 2026 · Updated Apr 2026

3/0 AWG XHHW-2 Copper Ampacity & Derating

Table 310.16 values are identical across NEC 2017, 2020, and 2023 editions.
3/0 AWG XHHW-2 copper is rated 225A at 90°C and 200A at 75°C per NEC 2023 Table 310.16. Most equipment terminations are rated 75°C, making 200A the practical limit. Suitable for 200A circuits.
90°C225A
75°C200A
Breaker200A
Conduit2" EMT
V-Drop/100ft1.3%
Ampacity Derating Walkthrough
Base Ampacity Table 310.16, 90°C
225A
Temp Correction 86°F × 1.0
225A
Bundling ≤3 CCC × 1.0
225A
Termination 110.14(C)(1)(b) 75°C
200A −11%
Usable Ampacity
200A
Common inspection failure: Using 225A (90°C) without accounting for the 75°C termination limit. Most panels and breakers are rated 75°C per 110.14(C). The usable ampacity is 200A, not 225A.

Calculation Walkthrough

Step 1Look Up Base Ampacity
Table 310.16

Per NEC 2023 Table 310.16, 3/0 AWG copper XHHW-2 (90°C column) = 225A base. Assumes ≤3 CCC at 30°C ambient.

Base =225A
Step 2Temperature Correction
Table 310.15(B)(1)

At 30.0°C (86°F), factor = 1.0. No reduction. At 50°C attic: factor drops to ~0.82 for 90°C insulation.

After temp =225A × 1.0 = 225A
Step 3Bundling Adjustment
Table 310.15(C)(1)

≤3 CCC = factor 1.0. EGC + neutral (unbalanced) not counted per 310.15(E). Typical 240V circuit: 2 hots + N + G = 2 CCC.

After bundling =225A × 1.0 = 225A
Step 4Termination Limit
110.14(C)(1)(b)

Equipment termination governs the final ampacity. Circuits >100A: 75°C column applies per 110.14(C)(1)(b). Modern panels and breakers are listed for 75°C terminations, so the 75°C column value of 200A becomes the ceiling. The 90°C rating is only used as the starting point for temperature correction and bundling derating. After all adjustments, the result cannot exceed the termination column value. This is the single most commonly failed inspection item.

Final =200A
Step 5Voltage Drop at 100 ft
210.19(A) Note 4

NEC recommends limiting voltage drop to 3% on branch circuits and 5% total (branch + feeder combined). For 3/0 AWG copper carrying 200A at 240V single-phase over a 100-foot one-way run: Vd = (2 × L × I × R) / 1000. The resistance per 1000 ft for 3/0 AWG copper at 75°C is used from NEC Chapter 9 Table 8. At 200A and 100 ft, the drop is 3.1V (1.3%). For longer runs or higher loads, use the voltage drop calculator with your specific distance and load.

V-Drop =1.3% (3.1V at 240V)

Common Applications

3/0 AWG XHHW-2 copper at 200A covers 165-200A feeders and is the Table 310.16 minimum for general 200A circuits at 75ยฐC (200A exactly). Paired with a 200A breaker. For 200A dwelling services, Table 310.15(B)(7) allows the smaller 2/0 AWG. In practice, some electricians prefer 4/0 AWG for 200A services to provide voltage drop margin on longer runs. Where 3/0 is the clear choice is in 175-200A commercial feeders and subpanel installations where Table 310.16 governs sizing.

Need more capacity? 4/0 AWG provides 230A. See also: copper vs aluminum.

NEC 2020 vs NEC 2023

Feature
20202023
Table #
310.15(B)(16)310.16
75°C
200A200A
90°C
225A225A
NEC 2020
Table 310.15(B)(16)
3/0 AWG Cu 75°C = 200A
3/0 AWG Cu 90°C = 225A
NEC 2023
Table 310.16 renumbered
3/0 AWG Cu 75°C = 200A
3/0 AWG Cu 90°C = 225A

Ampacity values for 3/0 AWG copper are identical across NEC 2017, 2020, and 2023 editions. The only change affecting this conductor is the table renumbering from Table 310.15(B)(16) to Table 310.16 in the 2023 edition. This renumbering was part of a broader reorganization of Article 310 that also moved temperature correction factors from Table 310.15(B)(2)(a) to Table 310.15(B)(1) and bundling adjustment factors from Table 310.15(B)(3)(a) to Table 310.15(C)(1). When citing NEC references on permits or inspection reports, use the table numbers that match your state's adopted code year. States on NEC 2020 or earlier should cite Table 310.15(B)(16); states that have adopted NEC 2023 should cite Table 310.16.

Quick Reference

ConductorTempAmpsUse
3/0 AWG Copper TW60°C165AWet / underground
3/0 AWG Copper THW75°C200AStandard circuits
3/0 AWG Copper THHN90°C225ADerating start only
3/0 AWG Copper free air75/90°C310A / 350ATable 310.17
3/0 AWG Aluminum THHN75°C155AAluminum equivalent
NEC 2026: Ampacity values for 3/0 AWG copper are unchanged. Table renumbering from 2023 is retained. See NEC 2026 changes for Article 310 updates as states begin adoption.

Frequently asked questions

What is the ampacity of 3/0 AWG Copper wire?

3/0 AWG XHHW-2 Copper has a base ampacity of 225A at 90°C per NEC 2023 Table 310.16. After applying the 110.14(C) termination temperature limit, the usable ampacity is 200A for most installations. This is the value you use for circuit sizing and breaker selection.

What size breaker do I need for 3/0 AWG copper wire?

Pair 3/0 AWG copper with a 200A breaker. The wire's usable ampacity of 200A must equal or exceed the breaker rating. For continuous loads (running 3+ hours), the load must not exceed 80% of the breaker rating (160A on a 200A breaker). See the full ampacity table for all wire sizes.

Can I use 3/0 AWG wire in conduit?

Yes. 3/0 AWG XHHW-2 is rated for conduit installations including EMT, PVC, and rigid metal conduit. The 225A base ampacity applies in conduit with no more than 3 current-carrying conductors. If bundling more than 3 conductors, apply the bundling adjustment factors from NEC Table 310.15(C)(1).

How far can I run 3/0 AWG copper wire?

The maximum distance depends on load and voltage. For 3/0 AWG copper at 200A on a 240V circuit, use the voltage drop calculator with your specific distance. As a rule of thumb, keep voltage drop under 3% for branch circuits. Longer runs may require upsizing the conductor.

Can I use aluminum instead of copper for 3/0 AWG?

Yes, but check the ampacity difference. 3/0 AWG aluminum XHHW-2 is rated at 155A versus 200A for copper. For equivalent capacity, you'll typically need to go up one or two gauge sizes in aluminum. See the 3/0 AWG copper vs aluminum comparison for cost and installation details.

Derating matrix: all conditions

Ampacity of 3/0 AWG copper XHHW-2 (225A base at 90°C) after temperature correction per 310.15(B)(1) and bundling adjustment per 310.15(C)(1). The usable limit after 110.14(C) is 200A.

Ambient °C1-3 CCC4-6 CCC7-9 CCC10-20 CCC
10°C (50°F)258A207A181A129A
15°C (59°F)252A201A176A126A
20°C (68°F)243A194A170A121A
25°C (77°F)234A187A163A117A
30°C (86°F)225A180A157A112A
35°C (95°F)216A172A151A108A
40°C (104°F)204A163A143A102A
45°C (113°F)195A156A137A97A
50°C (122°F)184A147A129A92A

At/above usable limit Below limit Severely restricted

Bottom line: In a hot attic (50ยฐC) with standard bundling, 3/0 AWG copper drops to 184A - a 18% loss from the 225A base rating. Worst case (50ยฐC, 20 conductors) drops to 92A, a 59% reduction. Use the ampacity calculator to check your exact conditions.
Requirements vary by state. NEC edition, licensing, permits, and GFCI rules differ by jurisdiction. Check your state or pick it below for personalized info across WireRef.
Important: For reference only. Not a substitute for a licensed electrician. Electrical work can cause serious injury, death, fire, or property damage if performed incorrectly. Always hire a licensed electrician for electrical work, especially for service upgrades, panel work, and 240V circuits. Values are derived from NFPA 70 (NEC) for educational purposes. Always verify against your locally adopted NEC edition and amendments - local jurisdictions may enforce stricter requirements. WireRef provides reference information only and is not responsible for work performed based on this content. NEC® is a registered trademark of the National Fire Protection Association. Free NEC access via NFPA · OSHA Electrical Safety · Terms of use.