ModerateNEC 2023 · 2026 · Updated Apr 2026

3/0 AWG THHN Aluminum Ampacity & Derating

Table 310.16 values are identical across NEC 2017, 2020, and 2023 editions.
3/0 AWG THHN aluminum is rated 175A at 90°C and 155A at 75°C per NEC 2023 Table 310.16. Most equipment terminations are rated 75°C, making 155A the practical limit. Suitable for 175A circuits.
90°C175A
75°C155A
Breaker175A
Conduit1-1/2" EMT
V-Drop/100ft1.6%
Ampacity Derating Walkthrough
Base Ampacity Table 310.16, 90°C
175A
Temp Correction 86°F × 1.0
175A
Bundling ≤3 CCC × 1.0
175A
Termination 110.14(C)(1)(b) 75°C
155A −11%
Usable Ampacity
155A
Common inspection failure: Using 175A (90°C) without accounting for the 75°C termination limit. Most panels and breakers are rated 75°C per 110.14(C). The usable ampacity is 155A, not 175A.

Calculation Walkthrough

Step 1Look Up Base Ampacity
Table 310.16

Per NEC 2023 Table 310.16, 3/0 AWG aluminum THHN (90°C column) = 175A base. Assumes ≤3 CCC at 30°C ambient.

Base =175A
Step 2Temperature Correction
Table 310.15(B)(1)

At 30.0°C (86°F), factor = 1.0. No reduction. At 50°C attic: factor drops to ~0.82 for 90°C insulation.

After temp =175A × 1.0 = 175A
Step 3Bundling Adjustment
Table 310.15(C)(1)

≤3 CCC = factor 1.0. EGC + neutral (unbalanced) not counted per 310.15(E). Typical 240V circuit: 2 hots + N + G = 2 CCC.

After bundling =175A × 1.0 = 175A
Step 4Termination Limit
110.14(C)(1)(b)

Equipment termination governs the final ampacity. Circuits >100A: 75°C column applies per 110.14(C)(1)(b). Modern panels and breakers are listed for 75°C terminations, so the 75°C column value of 155A becomes the ceiling. The 90°C rating is only used as the starting point for temperature correction and bundling derating. After all adjustments, the result cannot exceed the termination column value. This is the single most commonly failed inspection item.

Final =155A
Step 5Voltage Drop at 100 ft
210.19(A) Note 4

NEC recommends limiting voltage drop to 3% on branch circuits and 5% total (branch + feeder combined). For 3/0 AWG aluminum carrying 155A at 240V single-phase over a 100-foot one-way run: Vd = (2 × L × I × R) / 1000. The resistance per 1000 ft for 3/0 AWG aluminum at 75°C is used from NEC Chapter 9 Table 8. At 155A and 100 ft, the drop is 3.9V (1.6%). For longer runs or higher loads, use the voltage drop calculator with your specific distance and load.

V-Drop =1.6% (3.9V at 240V)

Common Applications

3/0 AWG THHN aluminum at 155A covers 165-200A feeders and is the Table 310.16 minimum for general 200A circuits at 75ยฐC (200A exactly). Paired with a 200A breaker. For 200A dwelling services, Table 310.15(B)(7) allows the smaller 2/0 AWG. In practice, some electricians prefer 4/0 AWG for 200A services to provide voltage drop margin on longer runs. Where 3/0 is the clear choice is in 175-200A commercial feeders and subpanel installations where Table 310.16 governs sizing.

Need more capacity? 4/0 AWG provides 180A. See also: copper vs aluminum.

NEC 2020 vs NEC 2023

Feature
20202023
Table #
310.15(B)(16)310.16
75°C
155A155A
90°C
175A175A
NEC 2020
Table 310.15(B)(16)
3/0 AWG Au 75°C = 155A
3/0 AWG Au 90°C = 175A
NEC 2023
Table 310.16 renumbered
3/0 AWG Au 75°C = 155A
3/0 AWG Au 90°C = 175A

Ampacity values for 3/0 AWG aluminum are identical across NEC 2017, 2020, and 2023 editions. The only change affecting this conductor is the table renumbering from Table 310.15(B)(16) to Table 310.16 in the 2023 edition. This renumbering was part of a broader reorganization of Article 310 that also moved temperature correction factors from Table 310.15(B)(2)(a) to Table 310.15(B)(1) and bundling adjustment factors from Table 310.15(B)(3)(a) to Table 310.15(C)(1). When citing NEC references on permits or inspection reports, use the table numbers that match your state's adopted code year. States on NEC 2020 or earlier should cite Table 310.15(B)(16); states that have adopted NEC 2023 should cite Table 310.16.

Quick Reference

ConductorTempAmpsUse
3/0 AWG Aluminum TW60°C130AWet / underground
3/0 AWG Aluminum THW75°C155AStandard circuits
3/0 AWG Aluminum THHN90°C175ADerating start only
3/0 AWG Aluminum free air75/90°C240A / 270ATable 310.17
3/0 AWG Copper THHN75°C200ACopper equivalent
NEC 2026: Ampacity values for 3/0 AWG aluminum are unchanged. Table renumbering from 2023 is retained. See NEC 2026 changes for Article 310 updates as states begin adoption.

Frequently asked questions

What is the ampacity of 3/0 AWG Aluminum wire?

3/0 AWG THHN Aluminum has a base ampacity of 175A at 90°C per NEC 2023 Table 310.16. After applying the 110.14(C) termination temperature limit, the usable ampacity is 155A for most installations. This is the value you use for circuit sizing and breaker selection.

What size breaker do I need for 3/0 AWG aluminum wire?

Pair 3/0 AWG aluminum with a 175A breaker. The wire's usable ampacity of 155A must equal or exceed the breaker rating. For continuous loads (running 3+ hours), the load must not exceed 80% of the breaker rating (140A on a 175A breaker). See the full ampacity table for all wire sizes.

Can I use 3/0 AWG wire in conduit?

Yes. 3/0 AWG THHN is rated for conduit installations including EMT, PVC, and rigid metal conduit. The 175A base ampacity applies in conduit with no more than 3 current-carrying conductors. If bundling more than 3 conductors, apply the bundling adjustment factors from NEC Table 310.15(C)(1).

How far can I run 3/0 AWG aluminum wire?

The maximum distance depends on load and voltage. For 3/0 AWG aluminum at 155A on a 240V circuit, use the voltage drop calculator with your specific distance. As a rule of thumb, keep voltage drop under 3% for branch circuits. Longer runs may require upsizing the conductor.

Derating matrix: all conditions

Ampacity of 3/0 AWG aluminum THHN (175A base at 90°C) after temperature correction per 310.15(B)(1) and bundling adjustment per 310.15(C)(1). The usable limit after 110.14(C) is 155A.

Ambient °C1-3 CCC4-6 CCC7-9 CCC10-20 CCC
10°C (50°F)201A161A140A100A
15°C (59°F)196A156A137A98A
20°C (68°F)189A151A132A94A
25°C (77°F)182A145A127A91A
30°C (86°F)175A140A122A87A
35°C (95°F)168A134A117A84A
40°C (104°F)159A127A111A79A
45°C (113°F)152A121A106A76A
50°C (122°F)143A114A100A71A

At/above usable limit Below limit Severely restricted

Bottom line: In a hot attic (50ยฐC) with standard bundling, 3/0 AWG aluminum drops to 143A - a 18% loss from the 175A base rating. Worst case (50ยฐC, 20 conductors) drops to 71A, a 59% reduction. Use the ampacity calculator to check your exact conditions.
Requirements vary by state. NEC edition, licensing, permits, and GFCI rules differ by jurisdiction. Check your state or pick it below for personalized info across WireRef.
Important: For reference only. Not a substitute for a licensed electrician. Electrical work can cause serious injury, death, fire, or property damage if performed incorrectly. Always hire a licensed electrician for electrical work, especially for service upgrades, panel work, and 240V circuits. Values are derived from NFPA 70 (NEC) for educational purposes. Always verify against your locally adopted NEC edition and amendments - local jurisdictions may enforce stricter requirements. WireRef provides reference information only and is not responsible for work performed based on this content. NEC® is a registered trademark of the National Fire Protection Association. Free NEC access via NFPA · OSHA Electrical Safety · Terms of use.

NEC 2023 references verified April 2026