ModerateNEC 2023 · 2026 · Updated Apr 2026

2/0 AWG THHN Aluminum Ampacity & Derating

Table 310.16 values are identical across NEC 2017, 2020, and 2023 editions.
2/0 AWG THHN aluminum is rated 150A at 90°C and 135A at 75°C per NEC 2023 Table 310.16. Most equipment terminations are rated 75°C, making 135A the practical limit. Suitable for 150A circuits.
90°C150A
75°C135A
Breaker150A
Conduit1-1/4" EMT
V-Drop/100ft1.8%
Ampacity Derating Walkthrough
Base Ampacity Table 310.16, 90°C
150A
Temp Correction 86°F × 1.0
150A
Bundling ≤3 CCC × 1.0
150A
Termination 110.14(C)(1)(b) 75°C
135A −10%
Usable Ampacity
135A
Common inspection failure: Using 150A (90°C) without accounting for the 75°C termination limit. Most panels and breakers are rated 75°C per 110.14(C). The usable ampacity is 135A, not 150A.

Calculation Walkthrough

Step 1Look Up Base Ampacity
Table 310.16

Per NEC 2023 Table 310.16, 2/0 AWG aluminum THHN (90°C column) = 150A base. Assumes ≤3 CCC at 30°C ambient.

Base =150A
Step 2Temperature Correction
Table 310.15(B)(1)

At 30.0°C (86°F), factor = 1.0. No reduction. At 50°C attic: factor drops to ~0.82 for 90°C insulation.

After temp =150A × 1.0 = 150A
Step 3Bundling Adjustment
Table 310.15(C)(1)

≤3 CCC = factor 1.0. EGC + neutral (unbalanced) not counted per 310.15(E). Typical 240V circuit: 2 hots + N + G = 2 CCC.

After bundling =150A × 1.0 = 150A
Step 4Termination Limit
110.14(C)(1)(b)

Equipment termination governs the final ampacity. Circuits >100A: 75°C column applies per 110.14(C)(1)(b). Modern panels and breakers are listed for 75°C terminations, so the 75°C column value of 135A becomes the ceiling. The 90°C rating is only used as the starting point for temperature correction and bundling derating. After all adjustments, the result cannot exceed the termination column value. This is the single most commonly failed inspection item.

Final =135A
Step 5Voltage Drop at 100 ft
210.19(A) Note 4

NEC recommends limiting voltage drop to 3% on branch circuits and 5% total (branch + feeder combined). For 2/0 AWG aluminum carrying 135A at 240V single-phase over a 100-foot one-way run: Vd = (2 × L × I × R) / 1000. The resistance per 1000 ft for 2/0 AWG aluminum at 75°C is used from NEC Chapter 9 Table 8. At 135A and 100 ft, the drop is 4.3V (1.8%). For longer runs or higher loads, use the voltage drop calculator with your specific distance and load.

V-Drop =1.8% (4.3V at 240V)

Common Applications

2/0 AWG THHN aluminum at 135A covers 145-175A feeders and is the NEC minimum for 200A dwelling services per Table 310.15(B)(7). Paired with a 175A breaker for general circuits, or used for 200A dwelling service entrance. At this conductor size, conduit fill and pulling tension become significant installation concerns. A typical 2/0 AWG pull in EMT requires 1-1/4" minimum for 3 conductors with ground. While 2/0 is the NEC minimum for 200A dwelling service, some electricians upsize to 4/0 AWG for voltage drop margin on longer runs. Check with your utility for their minimum conductor requirements, which may exceed NEC minimums.

Need more capacity? 3/0 AWG provides 155A. See also: copper vs aluminum.

NEC 2020 vs NEC 2023

Feature
20202023
Table #
310.15(B)(16)310.16
75°C
135A135A
90°C
150A150A
NEC 2020
Table 310.15(B)(16)
2/0 AWG Au 75°C = 135A
2/0 AWG Au 90°C = 150A
NEC 2023
Table 310.16 renumbered
2/0 AWG Au 75°C = 135A
2/0 AWG Au 90°C = 150A

Ampacity values for 2/0 AWG aluminum are identical across NEC 2017, 2020, and 2023 editions. The only change affecting this conductor is the table renumbering from Table 310.15(B)(16) to Table 310.16 in the 2023 edition. This renumbering was part of a broader reorganization of Article 310 that also moved temperature correction factors from Table 310.15(B)(2)(a) to Table 310.15(B)(1) and bundling adjustment factors from Table 310.15(B)(3)(a) to Table 310.15(C)(1). When citing NEC references on permits or inspection reports, use the table numbers that match your state's adopted code year. States on NEC 2020 or earlier should cite Table 310.15(B)(16); states that have adopted NEC 2023 should cite Table 310.16.

Quick Reference

ConductorTempAmpsUse
2/0 AWG Aluminum TW60°C115AWet / underground
2/0 AWG Aluminum THW75°C135AStandard circuits
2/0 AWG Aluminum THHN90°C150ADerating start only
2/0 AWG Aluminum free air75/90°C210A / 235ATable 310.17
2/0 AWG Copper THHN75°C175ACopper equivalent
NEC 2026: Ampacity values for 2/0 AWG aluminum are unchanged. Table renumbering from 2023 is retained. See NEC 2026 changes for Article 310 updates as states begin adoption.

Frequently asked questions

What is the ampacity of 2/0 AWG Aluminum wire?

2/0 AWG THHN Aluminum has a base ampacity of 150A at 90°C per NEC 2023 Table 310.16. After applying the 110.14(C) termination temperature limit, the usable ampacity is 135A for most installations. This is the value you use for circuit sizing and breaker selection.

What size breaker do I need for 2/0 AWG aluminum wire?

Pair 2/0 AWG aluminum with a 150A breaker. The wire's usable ampacity of 135A must equal or exceed the breaker rating. For continuous loads (running 3+ hours), the load must not exceed 80% of the breaker rating (120A on a 150A breaker). See the full ampacity table for all wire sizes.

Can I use 2/0 AWG wire in conduit?

Yes. 2/0 AWG THHN is rated for conduit installations including EMT, PVC, and rigid metal conduit. The 150A base ampacity applies in conduit with no more than 3 current-carrying conductors. If bundling more than 3 conductors, apply the bundling adjustment factors from NEC Table 310.15(C)(1).

How far can I run 2/0 AWG aluminum wire?

The maximum distance depends on load and voltage. For 2/0 AWG aluminum at 135A on a 240V circuit, use the voltage drop calculator with your specific distance. As a rule of thumb, keep voltage drop under 3% for branch circuits. Longer runs may require upsizing the conductor.

Derating matrix: all conditions

Ampacity of 2/0 AWG aluminum THHN (150A base at 90°C) after temperature correction per 310.15(B)(1) and bundling adjustment per 310.15(C)(1). The usable limit after 110.14(C) is 135A.

Ambient °C1-3 CCC4-6 CCC7-9 CCC10-20 CCC
10°C (50°F)172A138A120A86A
15°C (59°F)168A134A117A84A
20°C (68°F)162A129A113A81A
25°C (77°F)156A124A109A78A
30°C (86°F)150A120A105A75A
35°C (95°F)144A115A100A72A
40°C (104°F)136A109A95A68A
45°C (113°F)130A104A91A65A
50°C (122°F)122A98A86A61A

At/above usable limit Below limit Severely restricted

Bottom line: In a hot attic (50ยฐC) with standard bundling, 2/0 AWG aluminum drops to 122A - a 18% loss from the 150A base rating. Worst case (50ยฐC, 20 conductors) drops to 61A, a 59% reduction. Use the ampacity calculator to check your exact conditions.
Requirements vary by state. NEC edition, licensing, permits, and GFCI rules differ by jurisdiction. Check your state or pick it below for personalized info across WireRef.
Important: For reference only. Not a substitute for a licensed electrician. Electrical work can cause serious injury, death, fire, or property damage if performed incorrectly. Always hire a licensed electrician for electrical work, especially for service upgrades, panel work, and 240V circuits. Values are derived from NFPA 70 (NEC) for educational purposes. Always verify against your locally adopted NEC edition and amendments - local jurisdictions may enforce stricter requirements. WireRef provides reference information only and is not responsible for work performed based on this content. NEC® is a registered trademark of the National Fire Protection Association. Free NEC access via NFPA · OSHA Electrical Safety · Terms of use.

NEC 2023 references verified April 2026