ModerateNEC 2023 · 2026 · Updated Apr 2026

14 AWG NM-B Copper Ampacity & Derating

Table 310.16 values are identical across NEC 2017, 2020, and 2023 editions.

NEC Quick Answer

14 AWG NM-B copper is limited to 15A. Although the conductors inside NM-B cable are rated 90C, NEC 334.80 restricts NM-B to the 60C ampacity column. The maximum overcurrent protection is 15A per NEC 240.4(D). Note: a lower AWG number means a thicker wire, so 10 AWG is thicker than 14 AWG and carries more current.

NEC 2023: Table 310.16 (60C column), Section 334.80, Section 240.4(D)

14 AWG NM-B copper is rated 25A at 90°C and 15A at 60°C per NEC 2023 Table 310.16. Most equipment terminations are rated 60°C, making 15A the practical limit. Suitable for 15A circuits.
90°C25A
60°C15A
Breaker15A
Conduit1/2" EMT
V-Drop/100ft3.9%
Ampacity Derating Walkthrough
Base Ampacity Table 310.16, 90°C
25A
Temp Correction 86°F × 1.0
25A
Bundling ≤3 CCC × 1.0
25A
Termination 334.80 60°C
15A −40%
Usable Ampacity
15A
Common inspection failure: Using 25A (90°C) without accounting for the 60°C termination limit. Most panels and breakers are rated 60°C per 110.14(C). The usable ampacity is 15A, not 25A.

Calculation Walkthrough

Step 1Look Up Base Ampacity
Table 310.16

Per NEC 2023 Table 310.16, 14 AWG copper NM-B (90°C column) = 25A base. Assumes ≤3 CCC at 30°C ambient.

Base =25A
Step 2Temperature Correction
Table 310.15(B)(1)

At 30.0°C (86°F), factor = 1.0. No reduction. At 50°C attic: factor drops to ~0.82 for 60°C insulation.

After temp =25A × 1.0 = 25A
Step 3Bundling Adjustment
Table 310.15(C)(1)

≤3 CCC = factor 1.0. EGC + neutral (unbalanced) not counted per 310.15(E). Typical 240V circuit: 2 hots + N + G = 2 CCC.

After bundling =25A × 1.0 = 25A
Step 4Termination Limit
334.80

Equipment termination governs the final ampacity. Circuits ≤100A: use 60°C column unless conductor + equipment both rated 75°C. Modern panels and breakers are listed for 60°C terminations, so the 60°C column value of 15A becomes the ceiling. The 90°C rating is only used as the starting point for temperature correction and bundling derating. After all adjustments, the result cannot exceed the termination column value. This is the single most commonly failed inspection item.

Final =15A
Step 5Voltage Drop at 100 ft
210.19(A) Note 4

NEC recommends limiting voltage drop to 3% on branch circuits and 5% total (branch + feeder combined). For 14 AWG copper carrying 15A at 240V single-phase over a 100-foot one-way run: Vd = (2 × L × I × R) / 1000. The resistance per 1000 ft for 14 AWG copper at 75°C is used from NEC Chapter 9 Table 8. At 15A and 100 ft, the drop is 9.4V (3.9%). For longer runs or higher loads, use the voltage drop calculator with your specific distance and load.

V-Drop =3.9% (9.4V at 240V)

Common Applications

14 AWG NM-B copper at 15A covers general-purpose 15A lighting and receptacle circuits in residential and light commercial work. Paired with a 15A breaker, this is the minimum wire size permitted for branch circuits under NEC 240.4(D). Typical installations include bedroom and living room lighting, hallway receptacles, and switched outlets. In conduit runs, 14 AWG Copper NM-B handles multiple circuits per conduit without derating concerns when limited to 3 current-carrying conductors. For 20A circuits, upsize to 12 AWG. Note that some jurisdictions require 12 AWG minimum for all branch circuits regardless of load, so check your state adoption status.

Need more capacity? 12 AWG provides 20A. See also: copper vs aluminum.

NEC 2020 vs NEC 2023

Feature
20202023
Table #
310.15(B)(16)310.16
60°C
15A15A
90°C
25A25A
NEC 2020
Table 310.15(B)(16)
14 AWG Cu 60°C = 15A
14 AWG Cu 90°C = 25A
NEC 2023
Table 310.16 renumbered
14 AWG Cu 60°C = 15A
14 AWG Cu 90°C = 25A

Ampacity values for 14 AWG copper are identical across NEC 2017, 2020, and 2023 editions. The only change affecting this conductor is the table renumbering from Table 310.15(B)(16) to Table 310.16 in the 2023 edition. This renumbering was part of a broader reorganization of Article 310 that also moved temperature correction factors from Table 310.15(B)(2)(a) to Table 310.15(B)(1) and bundling adjustment factors from Table 310.15(B)(3)(a) to Table 310.15(C)(1). When citing NEC references on permits or inspection reports, use the table numbers that match your state's adopted code year. States on NEC 2020 or earlier should cite Table 310.15(B)(16); states that have adopted NEC 2023 should cite Table 310.16.

Quick Reference

ConductorTempAmpsUse
14 AWG Copper TW60°C15AWet / underground
14 AWG Copper THW75°C20AStandard circuits
14 AWG Copper THHN90°C25ADerating start only
14 AWG Copper free air75/90°C30A / 35ATable 310.17
NEC 2026: Ampacity values for 14 AWG copper are unchanged. Table renumbering from 2023 is retained. See NEC 2026 changes for Article 310 updates as states begin adoption.

Frequently asked questions

What is the ampacity of 14 AWG Copper wire?

14 AWG NM-B Copper has a base ampacity of 25A at 90°C per NEC 2023 Table 310.16. After applying the 110.14(C) termination temperature limit, the usable ampacity is 15A for most installations. This is the value you use for circuit sizing and breaker selection.

What size breaker do I need for 14 AWG copper wire?

Pair 14 AWG copper with a 15A breaker. The wire's usable ampacity of 15A must equal or exceed the breaker rating. For continuous loads (running 3+ hours), the load must not exceed 80% of the breaker rating (12A on a 15A breaker). See the full ampacity table for all wire sizes.

Can I use 14 AWG wire in conduit?

NM-B cable can be sleeved through short sections of conduit for physical protection per NEC 334.15(B), but it is not a standard conduit wiring method. For conduit installations, use individual THHN or XHHW-2 conductors instead. See Romex vs conduit and 14 AWG THHN for conduit ampacity.

How far can I run 14 AWG copper wire?

The maximum distance depends on load and voltage. For 14 AWG copper at 15A on a 240V circuit, use the voltage drop calculator with your specific distance. As a rule of thumb, keep voltage drop under 3% for branch circuits. Longer runs may require upsizing the conductor.

Derating matrix: all conditions

Ampacity of 14 AWG copper NM-B (25A base at 60°C) after temperature correction per 310.15(B)(1) and bundling adjustment per 310.15(C)(1). The usable limit after 110.14(C) is 15A.

Ambient °C1-3 CCC4-6 CCC7-9 CCC10-20 CCC
10°C (50°F)32A25A22A16A
15°C (59°F)30A24A21A15A
20°C (68°F)28A23A20A14A
25°C (77°F)27A21A18A13A
30°C (86°F)25A20A17A12A
35°C (95°F)22A18A15A11A
40°C (104°F)20A16A14A10A
45°C (113°F)17A14A12A8A
50°C (122°F)14A11A10A7A

At/above usable limit Below limit Severely restricted

Bottom line: In a hot attic (50°C) with standard bundling, 14 AWG copper drops to 14A - a 43% loss from the 25A base rating. Worst case (50°C, 20 conductors) drops to 7A, a 72% reduction. Use the ampacity calculator to check your exact conditions.
Requirements vary by state. NEC edition, licensing, permits, and GFCI rules differ by jurisdiction. Check your state or pick it below for personalized info across WireRef.
Important: For reference only. Not a substitute for a licensed electrician. Electrical work can cause serious injury, death, fire, or property damage if performed incorrectly. Always hire a licensed electrician for electrical work, especially for service upgrades, panel work, and 240V circuits. Values are derived from NFPA 70 (NEC) for educational purposes. Always verify against your locally adopted NEC edition and amendments - local jurisdictions may enforce stricter requirements. WireRef provides reference information only and is not responsible for work performed based on this content. NEC® is a registered trademark of the National Fire Protection Association. Free NEC access via NFPA · OSHA Electrical Safety · Terms of use.

NEC 2023 references verified April 2026

As an Amazon Associate, WireRef earns from qualifying purchases. Product links do not affect the reference data or recommendations on this site. Terms of use.