ModerateNEC 2023 · 2026 · Updated Apr 2026

12 AWG XHHW-2 Aluminum Ampacity & Derating

Table 310.16 values are identical across NEC 2017, 2020, and 2023 editions.
12 AWG XHHW-2 aluminum is rated 25A at 90°C and 20A at 75°C per NEC 2023 Table 310.16. Most equipment terminations are rated 75°C, making 20A the practical limit. Suitable for 15A circuits.
90°C25A
75°C20A
Breaker15A
Conduit1/2" EMT
V-Drop/100ft5.4%
Ampacity Derating Walkthrough
Base Ampacity Table 310.16, 90°C
25A
Temp Correction 86°F × 1.0
25A
Bundling ≤3 CCC × 1.0
25A
Termination 110.14(C)(1)(a)(2) 75°C
20A −20%
Usable Ampacity
20A
Common inspection failure: Using 25A (90°C) without accounting for the 75°C termination limit. Most panels and breakers are rated 75°C per 110.14(C). The usable ampacity is 20A, not 25A.

Calculation Walkthrough

Step 1Look Up Base Ampacity
Table 310.16

Per NEC 2023 Table 310.16, 12 AWG aluminum XHHW-2 (90°C column) = 25A base. Assumes ≤3 CCC at 30°C ambient.

Base =25A
Step 2Temperature Correction
Table 310.15(B)(1)

At 30.0°C (86°F), factor = 1.0. No reduction. At 50°C attic: factor drops to ~0.82 for 90°C insulation.

After temp =25A × 1.0 = 25A
Step 3Bundling Adjustment
Table 310.15(C)(1)

≤3 CCC = factor 1.0. EGC + neutral (unbalanced) not counted per 310.15(E). Typical 240V circuit: 2 hots + N + G = 2 CCC.

After bundling =25A × 1.0 = 25A
Step 4Termination Limit
110.14(C)(1)(a)(2)

Equipment termination governs the final ampacity. Circuits ≤100A: use 60°C column unless conductor + equipment both rated 75°C. Modern panels and breakers are listed for 75°C terminations, so the 75°C column value of 20A becomes the ceiling. The 90°C rating is only used as the starting point for temperature correction and bundling derating. After all adjustments, the result cannot exceed the termination column value. This is the single most commonly failed inspection item.

Final =20A
Step 5Voltage Drop at 100 ft
210.19(A) Note 4

NEC recommends limiting voltage drop to 3% on branch circuits and 5% total (branch + feeder combined). For 12 AWG aluminum carrying 20A at 240V single-phase over a 100-foot one-way run: Vd = (2 × L × I × R) / 1000. The resistance per 1000 ft for 12 AWG aluminum at 75°C is used from NEC Chapter 9 Table 8. At 20A and 100 ft, the drop is 13.0V (5.4%). For longer runs or higher loads, use the voltage drop calculator with your specific distance and load.

V-Drop =5.4% (13.0V at 240V)

Common Applications

12 AWG XHHW-2 aluminum at 20A covers 20A general-purpose and small-appliance circuits, making it the most commonly installed wire size in residential construction. Required for kitchen countertop circuits, bathroom receptacles, garage circuits, and laundry areas per NEC 210.11(C). Paired with a 20A breaker. In a typical home, 12 AWG Aluminum makes up more than half of all branch circuit wiring. XHHW-2 in conduit can use the 90ยฐC column as a starting point for derating calculations per Table 310.15(C)(1). For dedicated 30A appliance circuits like dryers and water heaters, upsize to 10 AWG.

Need more capacity? 10 AWG provides 30A. See also: copper vs aluminum.

NEC 2020 vs NEC 2023

Feature
20202023
Table #
310.15(B)(16)310.16
75°C
20A20A
90°C
25A25A
NEC 2020
Table 310.15(B)(16)
12 AWG Au 75°C = 20A
12 AWG Au 90°C = 25A
NEC 2023
Table 310.16 renumbered
12 AWG Au 75°C = 20A
12 AWG Au 90°C = 25A

Ampacity values for 12 AWG aluminum are identical across NEC 2017, 2020, and 2023 editions. The only change affecting this conductor is the table renumbering from Table 310.15(B)(16) to Table 310.16 in the 2023 edition. This renumbering was part of a broader reorganization of Article 310 that also moved temperature correction factors from Table 310.15(B)(2)(a) to Table 310.15(B)(1) and bundling adjustment factors from Table 310.15(B)(3)(a) to Table 310.15(C)(1). When citing NEC references on permits or inspection reports, use the table numbers that match your state's adopted code year. States on NEC 2020 or earlier should cite Table 310.15(B)(16); states that have adopted NEC 2023 should cite Table 310.16.

Quick Reference

ConductorTempAmpsUse
12 AWG Aluminum TW60°C15AWet / underground
12 AWG Aluminum THW75°C20AStandard circuits
12 AWG Aluminum THHN90°C25ADerating start only
12 AWG Aluminum free air75/90°C30A / 35ATable 310.17
12 AWG Copper THHN75°C25ACopper equivalent
NEC 2026: Ampacity values for 12 AWG aluminum are unchanged. Table renumbering from 2023 is retained. See NEC 2026 changes for Article 310 updates as states begin adoption.

Frequently asked questions

What is the ampacity of 12 AWG Aluminum wire?

12 AWG XHHW-2 Aluminum has a base ampacity of 25A at 90°C per NEC 2023 Table 310.16. After applying the 110.14(C) termination temperature limit, the usable ampacity is 20A for most installations. This is the value you use for circuit sizing and breaker selection.

What size breaker do I need for 12 AWG aluminum wire?

Pair 12 AWG aluminum with a 15A breaker. The wire's usable ampacity of 20A must equal or exceed the breaker rating. For continuous loads (running 3+ hours), the load must not exceed 80% of the breaker rating (12A on a 15A breaker). See the full ampacity table for all wire sizes.

Can I use 12 AWG wire in conduit?

Yes. 12 AWG XHHW-2 is rated for conduit installations including EMT, PVC, and rigid metal conduit. The 25A base ampacity applies in conduit with no more than 3 current-carrying conductors. If bundling more than 3 conductors, apply the bundling adjustment factors from NEC Table 310.15(C)(1).

How far can I run 12 AWG aluminum wire?

The maximum distance depends on load and voltage. For 12 AWG aluminum at 20A on a 240V circuit, use the voltage drop calculator with your specific distance. As a rule of thumb, keep voltage drop under 3% for branch circuits. Longer runs may require upsizing the conductor.

Derating matrix: all conditions

Ampacity of 12 AWG aluminum XHHW-2 (25A base at 90°C) after temperature correction per 310.15(B)(1) and bundling adjustment per 310.15(C)(1). The usable limit after 110.14(C) is 20A.

Ambient °C1-3 CCC4-6 CCC7-9 CCC10-20 CCC
10°C (50°F)28A23A20A14A
15°C (59°F)28A22A19A14A
20°C (68°F)27A21A18A13A
25°C (77°F)26A20A18A13A
30°C (86°F)25A20A17A12A
35°C (95°F)24A19A16A12A
40°C (104°F)22A18A15A11A
45°C (113°F)21A17A15A10A
50°C (122°F)20A16A14A10A

At/above usable limit Below limit Severely restricted

Bottom line: In a hot attic (50ยฐC) with standard bundling, 12 AWG aluminum drops to 20A - a 19% loss from the 25A base rating. Worst case (50ยฐC, 20 conductors) drops to 10A, a 60% reduction. Use the ampacity calculator to check your exact conditions.
Requirements vary by state. NEC edition, licensing, permits, and GFCI rules differ by jurisdiction. Check your state or pick it below for personalized info across WireRef.
Important: For reference only. Not a substitute for a licensed electrician. Electrical work can cause serious injury, death, fire, or property damage if performed incorrectly. Always hire a licensed electrician for electrical work, especially for service upgrades, panel work, and 240V circuits. Values are derived from NFPA 70 (NEC) for educational purposes. Always verify against your locally adopted NEC edition and amendments - local jurisdictions may enforce stricter requirements. WireRef provides reference information only and is not responsible for work performed based on this content. NEC® is a registered trademark of the National Fire Protection Association. Free NEC access via NFPA · OSHA Electrical Safety · Terms of use.

NEC 2023 references verified April 2026

As an Amazon Associate, WireRef earns from qualifying purchases. Product links do not affect the reference data or recommendations on this site. Terms of use.