10 AWG THHN Copper Ampacity & Derating

Table 310.16 values are identical across NEC 2017, 2020, and 2023 editions.

NEC Quick Answer

10 AWG copper THHN has a base ampacity of 40A at 90C per NEC Table 310.16. Usable ampacity is 35A after applying the 75C termination limit. Maximum overcurrent protection for 10 AWG copper is 30A per NEC 240.4(D).

NEC 2023: Table 310.16, Section 240.4(D), Section 110.14(C)

10 AWG THHN copper is rated 40A at 90°C and 35A at 75°C per NEC 2023 Table 310.16. Most equipment terminations are rated 75°C, making 35A the practical limit. Suitable for 30A circuits.
90°C40A
75°C35A
Breaker30A
Conduit3/4" EMT
V-Drop/100ft3.6%
Ampacity Derating Walkthrough
Base Ampacity Table 310.16, 90°C
40A
Temp Correction 86°F × 1.0
40A
Bundling ≤3 CCC × 1.0
40A
Termination 110.14(C)(1)(a)(2) 75°C
35A −12%
Usable Ampacity
35A
Common inspection failure: Using 40A (90°C) without accounting for the 75°C termination limit. Most panels and breakers are rated 75°C per 110.14(C). The usable ampacity is 35A, not 40A.

Calculation Walkthrough

Step 1Look Up Base Ampacity
Table 310.16

Per NEC 2023 Table 310.16, 10 AWG copper THHN (90°C column) = 40A base. Assumes ≤3 CCC at 30°C ambient.

Base =40A
Step 2Temperature Correction
Table 310.15(B)(1)

At 30.0°C (86°F), factor = 1.0. No reduction. At 50°C attic: factor drops to ~0.82 for 90°C insulation.

After temp =40A × 1.0 = 40A
Step 3Bundling Adjustment
Table 310.15(C)(1)

≤3 CCC = factor 1.0. EGC + neutral (unbalanced) not counted per 310.15(E). Typical 240V circuit: 2 hots + N + G = 2 CCC.

After bundling =40A × 1.0 = 40A
Step 4Termination Limit
110.14(C)(1)(a)(2)

Equipment termination governs the final ampacity. Circuits ≤100A: use 60°C column unless conductor + equipment both rated 75°C. Modern panels and breakers are listed for 75°C terminations, so the 75°C column value of 35A becomes the ceiling. The 90°C rating is only used as the starting point for temperature correction and bundling derating. After all adjustments, the result cannot exceed the termination column value. This is the single most commonly failed inspection item.

Final =35A
Step 5Voltage Drop at 100 ft
210.19(A) Note 4

NEC recommends limiting voltage drop to 3% on branch circuits and 5% total (branch + feeder combined). For 10 AWG copper carrying 35A at 240V single-phase over a 100-foot one-way run: Vd = (2 × L × I × R) / 1000. The resistance per 1000 ft for 10 AWG copper at 75°C is used from NEC Chapter 9 Table 8. At 35A and 100 ft, the drop is 8.7V (3.6%). For longer runs or higher loads, use the voltage drop calculator with your specific distance and load.

V-Drop =3.6% (8.7V at 240V)

Common Applications

10 AWG THHN copper at 35A covers 30A dedicated appliance circuits including electric dryers, water heaters, window air conditioning units, and small workshop equipment. Paired with a 30A breaker. The 10 AWG Copper conductor at 35A handles the continuous loads typical in these applications with margin to spare. For electric dryers, NEC 250.140 requires a 4-wire connection (2 hots, neutral, ground) in new construction. Water heater circuits are typically 240V with a 30A 2-pole breaker and no neutral. When installing in conduit runs exceeding 100 feet, verify voltage drop stays under 3%. For circuits above 30A such as electric ranges, upsize to 8 AWG.

Need more capacity? 8 AWG provides 50A. See also: copper vs aluminum.

NEC 2020 vs NEC 2023

Feature
20202023
Table #
310.15(B)(16)310.16
75°C
35A35A
90°C
40A40A
NEC 2020
Table 310.15(B)(16)
10 AWG Cu 75°C = 35A
10 AWG Cu 90°C = 40A
NEC 2023
Table 310.16 renumbered
10 AWG Cu 75°C = 35A
10 AWG Cu 90°C = 40A

Ampacity values for 10 AWG copper are identical across NEC 2017, 2020, and 2023 editions. The only change affecting this conductor is the table renumbering from Table 310.15(B)(16) to Table 310.16 in the 2023 edition. This renumbering was part of a broader reorganization of Article 310 that also moved temperature correction factors from Table 310.15(B)(2)(a) to Table 310.15(B)(1) and bundling adjustment factors from Table 310.15(B)(3)(a) to Table 310.15(C)(1). When citing NEC references on permits or inspection reports, use the table numbers that match your state's adopted code year. States on NEC 2020 or earlier should cite Table 310.15(B)(16); states that have adopted NEC 2023 should cite Table 310.16.

Quick Reference

ConductorTempAmpsUse
10 AWG Copper TW60°C30AWet / underground
10 AWG Copper THW75°C35AStandard circuits
10 AWG Copper THHN90°C40ADerating start only
10 AWG Copper free air75/90°C50A / 55ATable 310.17
10 AWG Aluminum THHN75°C30AAluminum equivalent
NEC 2026: Ampacity values for 10 AWG copper are unchanged. Table renumbering from 2023 is retained. See NEC 2026 changes for Article 310 updates as states begin adoption.

Frequently asked questions

What is the ampacity of 10 AWG Copper wire?

10 AWG THHN Copper has a base ampacity of 40A at 90°C per NEC 2023 Table 310.16. After applying the 110.14(C) termination temperature limit, the usable ampacity is 35A for most installations. This is the value you use for circuit sizing and breaker selection.

What size breaker do I need for 10 AWG copper wire?

Pair 10 AWG copper with a 30A breaker. The wire's usable ampacity of 35A must equal or exceed the breaker rating. For continuous loads (running 3+ hours), the load must not exceed 80% of the breaker rating (24A on a 30A breaker). See the full ampacity table for all wire sizes.

Can I use 10 AWG wire in conduit?

Yes. 10 AWG THHN is rated for conduit installations including EMT, PVC, and rigid metal conduit. The 40A base ampacity applies in conduit with no more than 3 current-carrying conductors. If bundling more than 3 conductors, apply the bundling adjustment factors from NEC Table 310.15(C)(1).

How far can I run 10 AWG copper wire?

The maximum distance depends on load and voltage. For 10 AWG copper at 35A on a 240V circuit, use the voltage drop calculator with your specific distance. As a rule of thumb, keep voltage drop under 3% for branch circuits. Longer runs may require upsizing the conductor.

Can I use aluminum instead of copper for 10 AWG?

Yes, but check the ampacity difference. 10 AWG aluminum THHN is rated at 30A versus 35A for copper. For equivalent capacity, you'll typically need to go up one or two gauge sizes in aluminum. See the 10 AWG copper vs aluminum comparison for cost and installation details.

Derating matrix: all conditions

Ampacity of 10 AWG copper THHN (40A base at 90°C) after temperature correction per 310.15(B)(1) and bundling adjustment per 310.15(C)(1). The usable limit after 110.14(C) is 35A.

Ambient °C1-3 CCC4-6 CCC7-9 CCC10-20 CCC
10°C (50°F)46A36A32A23A
15°C (59°F)44A35A31A22A
20°C (68°F)43A34A30A21A
25°C (77°F)41A33A29A20A
30°C (86°F)40A32A28A20A
35°C (95°F)38A30A26A19A
40°C (104°F)36A29A25A18A
45°C (113°F)34A27A24A17A
50°C (122°F)32A26A22A16A

At/above usable limit Below limit Severely restricted

Bottom line: In a hot attic (50°C) with standard bundling, 10 AWG copper drops to 32A - a 19% loss from the 40A base rating. Worst case (50°C, 20 conductors) drops to 16A, a 60% reduction. Use the ampacity calculator to check your exact conditions.
Requirements vary by state. NEC edition, licensing, permits, and GFCI rules differ by jurisdiction. Check your state or pick it below for personalized info across WireRef.
Important: For reference only. Not a substitute for a licensed electrician. Electrical work can cause serious injury, death, fire, or property damage if performed incorrectly. Always hire a licensed electrician for electrical work, especially for service upgrades, panel work, and 240V circuits. Values are derived from NFPA 70 (NEC) for educational purposes. Always verify against your locally adopted NEC edition and amendments - local jurisdictions may enforce stricter requirements. WireRef provides reference information only and is not responsible for work performed based on this content. NEC® is a registered trademark of the National Fire Protection Association. Free NEC access via NFPA · OSHA Electrical Safety · Terms of use.

NEC 2023 references verified April 2026