ModerateNEC 2023 · 2026 · Updated Apr 2026

1 AWG XHHW-2 Aluminum Ampacity & Derating

Table 310.16 values are identical across NEC 2017, 2020, and 2023 editions.
1 AWG XHHW-2 aluminum is rated 115A at 90°C and 100A at 75°C per NEC 2023 Table 310.16. Most equipment terminations are rated 75°C, making 100A the practical limit. Suitable for 100A circuits.
90°C115A
75°C100A
Breaker100A
Conduit1" EMT
V-Drop/100ft2.1%
Ampacity Derating Walkthrough
Base Ampacity Table 310.16, 90°C
115A
Temp Correction 86°F × 1.0
115A
Bundling ≤3 CCC × 1.0
115A
Termination 110.14(C)(1)(a)(2) 75°C
100A −13%
Usable Ampacity
100A
Common inspection failure: Using 115A (90°C) without accounting for the 75°C termination limit. Most panels and breakers are rated 75°C per 110.14(C). The usable ampacity is 100A, not 115A.

Calculation Walkthrough

Step 1Look Up Base Ampacity
Table 310.16

Per NEC 2023 Table 310.16, 1 AWG aluminum XHHW-2 (90°C column) = 115A base. Assumes ≤3 CCC at 30°C ambient.

Base =115A
Step 2Temperature Correction
Table 310.15(B)(1)

At 30.0°C (86°F), factor = 1.0. No reduction. At 50°C attic: factor drops to ~0.82 for 90°C insulation.

After temp =115A × 1.0 = 115A
Step 3Bundling Adjustment
Table 310.15(C)(1)

≤3 CCC = factor 1.0. EGC + neutral (unbalanced) not counted per 310.15(E). Typical 240V circuit: 2 hots + N + G = 2 CCC.

After bundling =115A × 1.0 = 115A
Step 4Termination Limit
110.14(C)(1)(a)(2)

Equipment termination governs the final ampacity. Circuits ≤100A: use 60°C column unless conductor + equipment both rated 75°C. Modern panels and breakers are listed for 75°C terminations, so the 75°C column value of 100A becomes the ceiling. The 90°C rating is only used as the starting point for temperature correction and bundling derating. After all adjustments, the result cannot exceed the termination column value. This is the single most commonly failed inspection item.

Final =100A
Step 5Voltage Drop at 100 ft
210.19(A) Note 4

NEC recommends limiting voltage drop to 3% on branch circuits and 5% total (branch + feeder combined). For 1 AWG aluminum carrying 100A at 240V single-phase over a 100-foot one-way run: Vd = (2 × L × I × R) / 1000. The resistance per 1000 ft for 1 AWG aluminum at 75°C is used from NEC Chapter 9 Table 8. At 100A and 100 ft, the drop is 5.1V (2.1%). For longer runs or higher loads, use the voltage drop calculator with your specific distance and load.

V-Drop =2.1% (5.1V at 240V)

Common Applications

1 AWG XHHW-2 aluminum at 100A covers 110-130A feeders and serves as a common choice for 125A subpanels or upgraded service feeds. Paired with a 110A or 125A breaker. At this conductor size, the cost difference between copper and aluminum becomes significant. A 1 AWG copper feeder may be 2-3x the material cost of the equivalent aluminum conductor (1/0 or 2/0 AWG Al for equivalent ampacity). For feeders to outbuildings, detached garages with heavy loads, or workshop subpanels requiring more than 100A, 1 AWG copper provides capacity without the conduit size increase required by larger gauges. Termination torque values increase at this size, so always use a calibrated torque wrench per manufacturer specifications.

Need more capacity? 1/0 AWG provides 120A. See also: copper vs aluminum.

NEC 2020 vs NEC 2023

Feature
20202023
Table #
310.15(B)(16)310.16
75°C
100A100A
90°C
115A115A
NEC 2020
Table 310.15(B)(16)
1 AWG Au 75°C = 100A
1 AWG Au 90°C = 115A
NEC 2023
Table 310.16 renumbered
1 AWG Au 75°C = 100A
1 AWG Au 90°C = 115A

Ampacity values for 1 AWG aluminum are identical across NEC 2017, 2020, and 2023 editions. The only change affecting this conductor is the table renumbering from Table 310.15(B)(16) to Table 310.16 in the 2023 edition. This renumbering was part of a broader reorganization of Article 310 that also moved temperature correction factors from Table 310.15(B)(2)(a) to Table 310.15(B)(1) and bundling adjustment factors from Table 310.15(B)(3)(a) to Table 310.15(C)(1). When citing NEC references on permits or inspection reports, use the table numbers that match your state's adopted code year. States on NEC 2020 or earlier should cite Table 310.15(B)(16); states that have adopted NEC 2023 should cite Table 310.16.

Quick Reference

ConductorTempAmpsUse
1 AWG Aluminum TW60°C85AWet / underground
1 AWG Aluminum THW75°C100AStandard circuits
1 AWG Aluminum THHN90°C115ADerating start only
1 AWG Aluminum free air75/90°C155A / 175ATable 310.17
1 AWG Copper THHN75°C130ACopper equivalent
NEC 2026: Ampacity values for 1 AWG aluminum are unchanged. Table renumbering from 2023 is retained. See NEC 2026 changes for Article 310 updates as states begin adoption.

Frequently asked questions

What is the ampacity of 1 AWG Aluminum wire?

1 AWG XHHW-2 Aluminum has a base ampacity of 115A at 90°C per NEC 2023 Table 310.16. After applying the 110.14(C) termination temperature limit, the usable ampacity is 100A for most installations. This is the value you use for circuit sizing and breaker selection.

What size breaker do I need for 1 AWG aluminum wire?

Pair 1 AWG aluminum with a 100A breaker. The wire's usable ampacity of 100A must equal or exceed the breaker rating. For continuous loads (running 3+ hours), the load must not exceed 80% of the breaker rating (80A on a 100A breaker). See the full ampacity table for all wire sizes.

Can I use 1 AWG wire in conduit?

Yes. 1 AWG XHHW-2 is rated for conduit installations including EMT, PVC, and rigid metal conduit. The 115A base ampacity applies in conduit with no more than 3 current-carrying conductors. If bundling more than 3 conductors, apply the bundling adjustment factors from NEC Table 310.15(C)(1).

How far can I run 1 AWG aluminum wire?

The maximum distance depends on load and voltage. For 1 AWG aluminum at 100A on a 240V circuit, use the voltage drop calculator with your specific distance. As a rule of thumb, keep voltage drop under 3% for branch circuits. Longer runs may require upsizing the conductor.

Derating matrix: all conditions

Ampacity of 1 AWG aluminum XHHW-2 (115A base at 90°C) after temperature correction per 310.15(B)(1) and bundling adjustment per 310.15(C)(1). The usable limit after 110.14(C) is 100A.

Ambient °C1-3 CCC4-6 CCC7-9 CCC10-20 CCC
10°C (50°F)132A105A92A66A
15°C (59°F)128A103A90A64A
20°C (68°F)124A99A86A62A
25°C (77°F)119A95A83A59A
30°C (86°F)115A92A80A57A
35°C (95°F)110A88A77A55A
40°C (104°F)104A83A73A52A
45°C (113°F)100A80A70A50A
50°C (122°F)94A75A66A47A

At/above usable limit Below limit Severely restricted

Bottom line: In a hot attic (50ยฐC) with standard bundling, 1 AWG aluminum drops to 94A - a 18% loss from the 115A base rating. Worst case (50ยฐC, 20 conductors) drops to 47A, a 59% reduction. Use the ampacity calculator to check your exact conditions.
Requirements vary by state. NEC edition, licensing, permits, and GFCI rules differ by jurisdiction. Check your state or pick it below for personalized info across WireRef.
Important: For reference only. Not a substitute for a licensed electrician. Electrical work can cause serious injury, death, fire, or property damage if performed incorrectly. Always hire a licensed electrician for electrical work, especially for service upgrades, panel work, and 240V circuits. Values are derived from NFPA 70 (NEC) for educational purposes. Always verify against your locally adopted NEC edition and amendments - local jurisdictions may enforce stricter requirements. WireRef provides reference information only and is not responsible for work performed based on this content. NEC® is a registered trademark of the National Fire Protection Association. Free NEC access via NFPA · OSHA Electrical Safety · Terms of use.

NEC 2023 references verified April 2026

As an Amazon Associate, WireRef earns from qualifying purchases. Product links do not affect the reference data or recommendations on this site. Terms of use.